The National Technical Information Service acquires, indexes, abstracts, and archives the largest collection of U.S. government-sponsored technical reports in existence. The NTRL offers online, free and open access to these authenticated government technical reports. Technical reports and documents in its repository may be available online for free either from the issuing federal agency, the U.S. Government Publishing Office’s Federal Digital System website, or through search engines.




Details
Actions:

Fatal Accident Circumstances and Epidemiology (FACE) Report: Apprentice Lineman Dies After Contacting 7200-Volt Primary Wire, May 2, 1989.


PB91217257

Publication Date 1989
Page Count 8
Abstract A 20 year old male apprentice lineman died after making direct contact with a 7200 volt primary wire. The victim was working for a large, multistate utility services contractor employing over 10,000 workers. The company has a multifaceted safety program that specifically addresses the hazards employees in each of the various subdivisions are likely to encounter. On the day of the accident it had been raining and all linework was thus cancelled. The rain stopped about noon and the victim and his crew leader went out to look at an area where they would be working the following day. The journeyman was not with the other two men but the crew leader decided they would go ahead and do the job that afternoon, allowing the apprentice to perform the job himself, a direct violation of the safety policy. After climbing the utility pole to begin the transfer of one primary and three secondary lines from an old utility pole to a new pole less than 18 inches away, the apprentice was electrocuted when he made contact with the 7200 volt primary line. The victim was wearing only his leather overgloves while attempting to install a section of line hose. The little fingers of both hands made contact with the energized primary wire. The path to ground was established from the victim's hands, through his body, to the metal climbers strapped to his legs. The victim's rubber gloves and a second pair of leather overgloves were in a tool pouch on his hip and a pair of rubber guards for his climbers were in the crew truck when the incident occurred.
Keywords
  • Occupational safety and health
  • Industrial safety
  • Safety measures
  • Environmental surveys
  • Accident investigations
  • Electrical shock
  • Protective equipment
  • Power transmission lines
  • Fatal Accident Circumstances and Epidemiology
  • EPA region 3
Source Agency
  • National Institute for Occupational Safety and Health
NTIS Subject Category
  • 57U - Public Health & Industrial Medicine
  • 57O - Pathology
  • 94H - Industrial Safety Engineering
Corporate Authors National Inst. for Occupational Safety and Health, Morgantown, WV. Div. of Safety Research.
Document Type Technical Report
NTIS Issue Number 199120
Fatal Accident Circumstances and Epidemiology (FACE) Report: Apprentice Lineman Dies After Contacting 7200-Volt Primary Wire, May 2, 1989.
Fatal Accident Circumstances and Epidemiology (FACE) Report: Apprentice Lineman Dies After Contacting 7200-Volt Primary Wire, May 2, 1989.
PB91217257

  • Occupational safety and health
  • Industrial safety
  • Safety measures
  • Environmental surveys
  • Accident investigations
  • Electrical shock
  • Protective equipment
  • Power transmission lines
  • Fatal Accident Circumstances and Epidemiology
  • EPA region 3
  • National Institute for Occupational Safety and Health
  • 57U - Public Health & Industrial Medicine
  • 57O - Pathology
  • 94H - Industrial Safety Engineering
Loading