The National Technical Information Service acquires, indexes, abstracts, and archives the largest collection of U.S. government-sponsored technical reports in existence. The NTRL offers online, free and open access to these authenticated government technical reports. Technical reports and documents in its repository may be available online for free either from the issuing federal agency, the U.S. Government Publishing Office’s Federal Digital System website, or through search engines.




Details
Actions:
Download PDFDownload PDF
Download

Bipolar HVDC Transmission System Study Between +- 600 Kv and +- 1200 Kv: Insulation Studies. Final Report.


EPRIEL395

Publication Date 1976
Personal Author Menemenlis, C.; Harbec, G.
Page Count 47
Abstract The insulation strengths for line and station insulators tested with various switching surges in the presence of dc voltage bias are described. This is part of a larger research effort to pinpoint technical problem areas in overhead line design and operation at voltages of +-600 kV to +-1200 kV. The results reported can be used to determine conductor-to-tower clearances, length of the insulator column supporting a station bus, and clearances between buses. In testing station buses it was observed that the presence of the second bus, which is connected to ground or is under a negative bias voltage, affects the level of voltage needed to produce a breakdown across the insulator column supporting the first bus. Bus height above ground also affects the breakdown voltage across the insulator column and between buses. In order to assure that all bus-to-ground breakdowns terminate on the lower part of the insulator column and not to the ground plane, a proper coordination between insulator column length and bus height above ground should be maintained. Because of the many parameters affecting the breakdown voltage of air gaps, and the preliminary nature of this research investigation, the results obtained should be considered ''typical'' and should not be used for final specification of air insulating clearances. When testing with mixed voltages, the breakdown voltage decreased for the conductor-to-tower arrangement as the impulse component was increased. On the other hand, the flashover voltage increased for the bus-to-bus arrangement with an increasing impulse component. These apparent inconsistencies were not expected from the limited amount of existing data. No reasonable explanation was developed. Power supply requirements for dc insulator contamination tests have also been investigated. Separate reports contain the results of this work. (ERA citation 03:003225)
Keywords
  • Ehv dc systems
  • Electrical insulators
  • Power transmission lines
  • Power transmission towers
  • Uhv dc systems
  • Breakdown
  • Electrical insulation
  • Flashover
  • Performance
  • Performance testing
  • Surges
  • ERDA/200302
  • Canada
  • Electric power transmission
Source Agency
  • Non Funded ERDA Documents From ERDA Tape
NTIS Subject Category
  • 97E - Electric Power Transmission
  • 49G - Resistive, Capacitive, & Inductive Components
Corporate Authors Hydro-Quebec, Varennes (Quebec). Research Inst.
Document Type Technical Report
NTIS Issue Number 197806
Bipolar HVDC Transmission System Study Between +- 600 Kv and +- 1200 Kv: Insulation Studies. Final Report.
Bipolar HVDC Transmission System Study Between +- 600 Kv and +- 1200 Kv: Insulation Studies. Final Report.
EPRIEL395

  • Ehv dc systems
  • Electrical insulators
  • Power transmission lines
  • Power transmission towers
  • Uhv dc systems
  • Breakdown
  • Electrical insulation
  • Flashover
  • Performance
  • Performance testing
  • Surges
  • ERDA/200302
  • Canada
  • Electric power transmission
  • Non Funded ERDA Documents From ERDA Tape
  • 97E - Electric Power Transmission
  • 49G - Resistive, Capacitive, & Inductive Components
Loading