The National Technical Information Service acquires, indexes, abstracts, and archives the largest collection of U.S. government-sponsored technical reports in existence. The NTRL offers online, free and open access to these authenticated government technical reports. Technical reports and documents in its repository may be available online for free either from the issuing federal agency, the U.S. Government Publishing Office’s Federal Digital System website, or through search engines.




Details
Actions:
Download PDFDownload XML
Download

Converging Redundant Sensor Network Information for Improved Building Control. Technical progress Report, December 1, 2003- November 30, 2004.


DE2005837829

Publication Date 2004
Personal Author Tiller, D. K.; Henze, G. P.
Page Count 38
Abstract Knowing how many people occupy a building, and where they are located, is a key component of building energy management and security. Commercial, industrial and residential buildings often incorporate systems used to determine occupancy, however, current sensor technology and control algorithms limit the effectiveness of both energy management and security systems. This topical report describes results from the first phase of a project to design, implement, validate, and prototype new technologies to monitor occupancy, control indoor environment services, and promote security in buildings. Phase I of the project focused on instrumentation and data collection. In this project phase a new occupancy detection system was developed, commissioned and installed in a sample of private offices and open-plan office workstations. Data acquisition systems were developed and deployed to collect data on space occupancy profiles. Analysis tools based on Bayesian probability theory were applied to the occupancy data generated by the sensor network. The inference of primary importance is a probability distribution over the number of occupants and their locations in a building, given past and present sensor measurements. Inferences were computed for occupancy and its temporal persistence in individual offices as well as the persistence of sensor status. The raw sensor data were also used to calibrate the sensor belief network, including the occupancy transition matrix used in the Markov model, sensor sensitivity, and sensor failure models. This study shows that the belief network framework can be applied to the analysis of data streams from sensor networks, offering significant benefits to building operation compared to current practice.
Keywords
  • Residential buildings
  • Energy management
  • Data acquisition systems
  • Algorithms
  • Design
  • Detection
  • Monitors
  • Occupants
  • Probability
  • Security
  • Sensitivity
Source Agency
  • Technical Information Center Oak Ridge Tennessee
Corporate Authors Nebraska Univ., Lincoln. Coll. of Engineering and Technology.; Department of Energy, Washington, DC.
Supplemental Notes Sponsored by Department of Energy, Washington, DC.
Document Type Technical Report
NTIS Issue Number 200523
Converging Redundant Sensor Network Information for Improved Building Control. Technical progress Report, December 1, 2003- November 30, 2004.
Converging Redundant Sensor Network Information for Improved Building Control. Technical progress Report, December 1, 2003- November 30, 2004.
DE2005837829

  • Residential buildings
  • Energy management
  • Data acquisition systems
  • Algorithms
  • Design
  • Detection
  • Monitors
  • Occupants
  • Probability
  • Security
  • Sensitivity
  • Technical Information Center Oak Ridge Tennessee
Loading