The National Technical Information Service acquires, indexes, abstracts, and archives the largest collection of U.S. government-sponsored technical reports in existence. The NTRL offers online, free and open access to these authenticated government technical reports. Technical reports and documents in its repository may be available online for free either from the issuing federal agency, the U.S. Government Publishing Office’s Federal Digital System website, or through search engines.




Details
Actions:
Download PDFDownload XML
Download

Alternate High Efficiency Particulate Air (HEPA) Filtration System. Phase IIA Final Report, September 29, 1999-September 30, 2002.


DE2004834563

Publication Date 2002
Personal Author Bishop, B.; Goldsmith, R.; Nielsen, K.; Paquette, P.
Page Count 194
Abstract In Phase IIA of this project, CeraMem has further developed and scaled up ceramic HEPA filters that are appropriate for use on filtration of vent gas from HLW tanks at DOE sites around the country. This work included procuring recrystallized SiC monoliths, developing membrane and cement materials, and defining a manufacturing process for the production of prototype full sizes HEPA filters. CeraMem has demonstrated that prototype full size filters can be manufactured by producing 9 full size filters that passed DOP aerosol testing at the Oak Ridge Filter Test Facility. One of these filters was supplied to the Savannah River Technical Center (SRTC) for process tests using simulated HLW tank waste. SRTC has reported that the filter was regenerable (with some increase in pressure drop) and that the filter retained its HEPA retention capability. CeraMem has also developed a Regenerable HEPA Filter System (RHFS) design and acceptance test plan that was reviewed by DOE personnel. The design and acceptance test plan form the basis of the system proposal for follow-on work in Phase IIB of this project.
Keywords
  • Filtration
  • Particulates
  • Air filters
  • Efficiency
  • Nuclear facilities
  • Design
  • Storage facilities
  • Off-gas systems
  • Radioactive waste storage
  • Pressure drop
  • Performance testing
  • High-level radioactive wastes
  • Regeneration
Source Agency
  • Technical Information Center Oak Ridge Tennessee
Corporate Authors CeraMem Corp., Waltham, MA.; Department of Energy, Washington, DC.
Supplemental Notes Sponsored by Department of Energy, Washington, DC.
Document Type Technical Report
NTIS Issue Number 200516
Alternate High Efficiency Particulate Air (HEPA) Filtration System. Phase IIA Final Report, September 29, 1999-September 30, 2002.
Alternate High Efficiency Particulate Air (HEPA) Filtration System. Phase IIA Final Report, September 29, 1999-September 30, 2002.
DE2004834563

  • Filtration
  • Particulates
  • Air filters
  • Efficiency
  • Nuclear facilities
  • Design
  • Storage facilities
  • Off-gas systems
  • Radioactive waste storage
  • Pressure drop
  • Performance testing
  • High-level radioactive wastes
  • Regeneration